HOME > Power Conditioner > UPS Devices > Off-Line UPS

Features :

WIDE INPUT RANGE, ALL MODELS WITH A.V.R. BUILT-IN

PWM REGULATED OUTPUT

LOW BATTERY AUTO-SHUTDOWN

OVER LOAD AUTO-SHUTDOWN

SHORT CIRCUIT PROTECTION

BATTERY & LOAD LEVEL DISPLAY

DB-9 INTERFACE CONNECTOR

Technical Specifications :
Model
NS-A601
NS-A102
NS-A152
NS-A202
Capacity
Power Rating
600VA
1000VA
1500VA
2000VA
Input
Voltage
110 / 115 / 120 / 220 / 230 / 240 Vac 25%
Frequency
50Hz or 60Hz 3Hz
Output
Voltage
110 / 115 / 120 / 220 / 230 / 240 Vac 5% (Adjustable)
Frequency
50Hz or 60Hz 1Hz
Waveform
PWM Simulated Sine wave
Voltage Regulation
3%
Power Factor
0.6
Transfer Time
2-4 msec
Battery
Voltage
12 Vdc
24 Vdc
48 Vdc
48 Vdc
Type
Sealed lead-acid, maintenance free
Back-up Time
6-45 minutes, depending on the load condition
Recharge Time
10 hours to 90% capacity.
Protection
Over Voltage
AC I / P > 25%
Under Voltage
AC I / P < 25% (Adjustable)
EMI / RFI
Meet EN50091-2 / EN61000-3-2 / EN61000-3-3 or FCC Part 15 Class A
Surge
Surge suppression meet IEEE-587 Category A varistor clamping 480 joules at 5ns response.
Overload
Fuse & Current Limited
Short Circuit
Fuse & Current Limited & Cut-off
Batt. Low Cut-off
Two stages, no battery drain after cut-off
Audible Alarm
Battery Discharge
Sounding every two seconds after mains fail
Final Discharge
Sounding once every second as battery approaches
Overload and Short
Continuously
Indicator
LED
Line Input (steady on)
Battery Mode (Slow blinking)
Battery Low (Fast blinking)
Overload / Short / UPS cut-off (LED off)
Normal
Back-up
AVR
Cut-off
Load Level
Battery Level
Interface
DB-9
Communication
AC fault, battery low, remote shutdown UPS
Environment
Operation Temp.
0-40 degree C, 32-104 degree F
Relative Humidity
0-90% non-condensing
Audible Noise
Less than 40 dB (at 1 meter)
Physical
Outlet
115V (NEMA 5-15R)
2
3
3
3
230V (IEC320)
2
3
3
3
Net Weight (KGS)
6.5
11.5
19
21
Dimension
W x H x D (mm)
89 x 170 x 266
89 x 170 x 385
143 x 197 x 408